IEC-60870-5-104 (104S) Protocol Implementation

104S v2 ♦ ProLinx Gateway

Protocol Manual

(Firmware v2.xx)


ProSoft Technology, Inc.

Page 77 of 157

The protocol specification explains that the qualifier value for these commands
should be configured as:

Bits Value

Description


1 to 6

0 Not

Used

1

Threshold Value (Deadband)

2

Smoothing Factor (filter time constant) - Not Supported

3

Low Limit Transmission of Measured Value

4

High Limit Transmission of Measured Value

5..31 Reserved

7 0 No

Change

1 Change

8 0 Operation

1

Not in Operation

For the 104S v2 gateway, the Low Limit and High Limit parameters cannot be
changed by command, because these values are calculated as follows:

Low Limit = (LAST REPORTED VALUE) - Deadband

High Limit = (LAST REPORTED VALUE) + Deadband

These commands must be sent to a specific Information Object Address. The
104S v2 gateway associates each Monitor Measured point with a Parameter
point using Parameter Offset entries: