104S v2 ♦ ProLinx Gateway

IEC-60870-5-104 (104S) Protocol Implementation

(Firmware v2.xx)

Protocol Manual


Page 60 of 157

ProSoft Technology, Inc.

March 19, 2010

Monitored Measured Normalized points use a data representation defined by the
protocol specification to represent fractional decimal values. The following table
describes the value for each bit as a reciprocal power of two (2), that is two (2)
raised to the power of a negative exponent ( -1 through -15). Bit 15 is the Sign
Bit.

Bit 15 14 13 12 11

10 9 8 7 6 5 4 3 2 1 0

Value
Hex
Decima

l

S 2

-1

2

-2

2

-3

2

-4

2

-5

2

-6

2

-7

2

-8

2

-9

2

-10

2

-11

2

-12

2

-13

2

-14

2

-15

4000h
0.5

0

1 0 0 0 0 0 0 0 0 0 0 0 0 0 0

2000h
0.25

0

0 1 0 0 0 0 0 0 0 0 0 0 0 0 0

1000h
0.125

0

0 0 1 0 0 0 0 0 0 0 0 0 0 0 0

6000h
0.75

0

1 1 0 0 0 0 0 0 0 0 0 0 0 0 0

3210h
0.3957
519531

25

0

0 1 1 0 0 1 0 1 0 1 0 1 0 0 0

Examples:

A value of 4000hex (only Bit 14 set, all others clear) is interpreted as 0.5 decimal

A value of 2000hex (only Bit 13 set, all others clear) is interpreted as 0.25
decimal

A value of 1000hex (only Bit 12 set, all others clear) is interpreted as 0.125
decimal

... and so on until...

A value of 0001hex (Only Bit 0 set, all others clear) is interpreted as
0.000030517578125

Therefore, the actual data values transmitted may be any combination of the
decimal values for any given bit pattern.