Verifying the transfer, Restoring (uploading) memory from computer to cont – High End Systems High End LCD Controller for Studio Color User Manual

Page 182

Advertising
background image

7-20

IBM-Compatible

Studio Color LCD Controller

Verifying the Transfer

Make sure the memory was backed up properly using either
Windows File Manager (or Explorer) or the DOS dir
command. The file should be about 256KB in size. If so,
you are finished.

If the file is smaller than 256KB, some problem occurred
during the transfer. Follow the troubleshooting suggestions
below:

If the file was larger than 0KB but less than 256KB, the
most likely cause was that something interrupted the
transfer. Check the cable connections on both ends,
verify the cable or replace it with a known working cable.
Begin again with the section titled “Initial Setup” on page
7-15,
making sure you do not press either the

<ESC>

key

on your computer or the

<Select>

key on the controller

until the transfer is complete.

If the file was 0KB, the most likely reason is you selected
the wrong serial (COM) port. You should also check the
cable connections on both ends, verify the cable or
replace it with a known working cable. Begin again with
the section titled “Initial Setup” on page 7-15, making
sure you select the correct COM port.

Restoring (Uploading) Memory from
Computer to Controller

Before following this procedure, you must have already
followed the instructions in the following sections:

“Connecting the Computer and Controller” on page 7-14

“Initial Setup” on page 7-15

Advertising