3 operation as backup controller, Operation as backup controller -15 – YSI IQ SensorNet 2020 XT Terminal User Manual

Page 21

Advertising
background image

System 2020 XT USB

Overview

1 - 15

ba76019e01

12/2012

1.3.3

Operation as backup controller

Automatic backup

function

If the MIQ/TC 2020 XT is configured as a terminal, it has a backup
controller that assumes the basic functions of the IQ S

ENSOR

N

ET

controller in the case of its failure. Thus the operating safety of the
system is considerably increased. For these purposes the MIQ/
TC 2020 XT regularly and automatically saves the system
configuration during the normal terminal operation.

System configuration

The system configuration incudes the following allocations and
settings:

Settings of sensors and diff. sensors

Settings of outputs and links

Edit list of sensors

Edit list of outputs

Measured value recording (datalogger settings)

 List of all components including software versions but without

terminal information.

 Application-related sensor calibration (e.g. matrix adjustment)

In the IQ S

ENSOR

N

ET

, the system configuration is stored in the

controller (MIQ/TC 2020 XT).

Functions of the MIQ/

TC 2020 XT

when operating as a

backup controller

If the MIQ/TC 2020 XT operates as a backup controller, all basic
IQ S

ENSOR

N

ET

functions are carried out. Relay interfaces and current

interfaces, PROFIBUS, Modbus and RS485 work without restrictions.

Restrictions of the MIQ/

TC 2020 XT

when operating as a

backup controller

The following functions are not supported:

 Continuation of the data logger operation of the main controller

 Continuation of the modem communication of the main controller if

the modem is connected to the interface of the MIQ/TC 2020 XT
(configured as controller).
A redundant data logging function can be set up with the aid of the
MIQ/IF232 interface module.

Manual backup function

In addition to the automatic backup of the system configuration you can
manually store the system configuration on a USB memory device at
any time. In the case of a system failure you can then transfer the
stored configuration from the USB memory device to another controller.

Advertising