SETUP

Table 11. Alarm Settings Menu

Middle

Display

Bottom

Display

Entry Description

ACTION

LATCHING

NO LATCH

= Relay assigned to alarm will trip (deenergize)

when the alarm occurs and release
(energize) when alarm is acknowledged

= Relay assigned to alarm will trip (deenergize)

when the alarm occurs and release
(energize) when alarm trip condition,
including hysteresis, is no longer present

ACTION

LATCHING

NO LATCH

= Relay assigned to alarm will trip (de-

energize) when the alarm occurs and release
(energize) when alarm is acknowledged

= Relay assigned to alarm will trip (de-

energize) when the alarm occurs and release
(energize) when alarm trip condition,
including hysteresis, is no longer present

SETUP

None.

TYPE

NONE

PROC HI
PROC LO

DEV HI
DEV LO

INP2 HI
INP2 LO

OUT HI
OUT LO

= Not used
= High process variable
= Low process variable
= High deviation
= Low deviation
= High input 2
= Low input 2
= High output
= Low output

IN HEAT

NO

YES

= Select cooling band as location for trip-point
= Select heating band as location for trip-point

TRIP

xxxx

In engineering units. Range:

PROC HI

–2995 to 30000

PROC LO

–3000 to 29995

DEV HI

1 to 30000

DEV LO

1 to 30000

INP2 HI

–2995 to 30000

INP2 LO

–3000 to 30000

OUT HI

‘MA. OUTP’ output limits

OUT LO

‘MA. OUTP’ output limits