Micromod MOD: Modcell 2050R Users Guide User Manual
Page 59

IB-23C650
SETUP
Table 2. Input Setup Menu
Middle
Display
Bottom
Display
Entry Description
OPTION
MANUAL
LAST
= Makes instrument return to the manual
mode after the input failure is corrected.
= Makes instrument return to the mode it was
in when the input failure occurred.
SETUP
If input 2 is being used as a remote bias or
ratio value input, the value will be displayed as
follows: xxx.xx.
UNITS
CELSIUS
FAHRENHT
= Celsius
= Fahrenheit
MA. HI
or
MV. HI
or
VOLTS HI
or
POSITION
xx.xx
xx.x
x.xx
x.xxx
1.00 to 54.00 mA dc
–8.0 to 120 mV dc
0.1 to 6.00 V dc
0.100 to 1.000 (wiper position)
MA. LO
or
MV. LO
or
VOLTS LO
or
POSITION
xx.xx
xx.x
x.xx
x.xxx
0.00 to 53.00 mA dc (minimum span = 1.00)
–10.0 to 118 mV dc (minimum span = 2.0)
0.00 to 5.90 V dc (minimum span = .10)
0.000 to 0.900 (wiper position)
(minimum span = .100)
LIN TYPE
NONE
SQR ROOT
When SQR ROOT linearization is selected, the
engineering units low value defaults to zero and
will not appear in this menu.
53