BASIC OPERATION
Automatic Operation with Remote or Multiple Set-Points
The controller may be in either auto or manual as selected in the power up
mode section of the BASE CFG MENU. If the controller is in automatic, the
front face will resemble the example below.
Note: Remote set-point requires the option board be installed.
[AUT] indicates that the controller is in
automatic.
The set-point may be [LOC], [LO2],
[LO3], [LO4] or [REM], depending on
which set-points were enabled in the
SETPTS MENU.
Bottom status display indicates lower
engineering display is showing the
current set-point and its engineering
units label.
Press
DN
or
UP
to change set-point
variable .
Press the scroll key to display the
output in percent in the lower
engineering display.
[OUT] appears in the third status
display (output cannot be changed in
automatic).
H or C indicates Heat or Cool if
controller was configured for heat/cool
operation.
Press the scroll key again to return the
set-point in the lower engineering
display.
133