Micromod MOD: Modcell 2050R Users Guide User Manual
Page 216

IB-23C650
CALIBRATION DATA
Table 15. Main/Option Board Calibration (Base Configuration Menu)
Step
Step Description
Top
Display
17
Option Board Calibration. Constants
UP
begins calibration at Step 17.1.
SCRL
advances to step 18, Default Database
entry point, in BASE CFG MENU (Table 1).
OPTN BRD
17.1
Input 2 Voltage Ref. High
UP
begins entry at most significant digit. Use
UP
or
DN
to set the digit, then
SCRL
to scroll to the
next digit. Repeat for all digits.
SCRL
advances to:
Step 17.1.1 if value was changed.
Step 17.2 otherwise.
INPUT 2
17.1.1
Are You Sure You Want to Change Input 2 Vref
Hi?
UP
selects YES or
DN
selects NO.
SCRL
advances to:
Step 17.1 on NO.
Step 17.2 on YES.
ARE YOU
17.2
Input 2 Voltage Ref. Lo
UP
begins entry at most significant digit. Use
UP
or
DN
to set the digit, then
SCRL
to scroll to the
next digit. Repeat for all digits.
SCRL
advances to:
Step 17.2.1 if value was changed.
Step 17.3. otherwise.
INPUT 2
17.2.1
Are You Sure You Want to Change Input 2 Vref
Lo?
UP
selects YES or
DN
selects NO.
SCRL
advances to:
Step 17.2 on NO.
Step 17.3 on YES.
ARE YOU
210