Table 2. Input Setup Menu

Middle

Display

Bottom

Display

Entry Description

UNITS HI

xxxx

–3000 to 30000 for mV, V, mA, and slidewire

(minimum span = 2)

For thermocouple range limits, see thermo-
couple input specification on page 12.

(minimum span for:
types B, R, and S = 300°C, 540°F
types E, J, K, N, and T = 100°C, 180°F)

For RTD range limits, see RTD input
specifications on page 13.

(minimum span = 20°C, 36°F)

See description on Process Input Engineering
Units High, Step 3.5.

UNITS LO

xxxx

–3000 to 30000

Notes:

Low value fixed at 0 when input 2
linearization type is SQR ROOT.

Hi and Lo units decimal points are
positioned at xxx.xx when a remote
ratio is configured.

55