Micromod MOD: Modcell 2050R Users Guide User Manual

Page 73

Advertising
background image

IB-23C650

SETUP

Table 3. Digital Input Setup Menu

Middle

Display

Bottom

Display

Entry Description

FUNCTION

NONE

AUTO/MAN
ALRM ACK
TOTALIZE
RAMPSOAK
SETP SEL
OUTP TRK

= Not used
= Switch control mode
= Global alarm acknowledge
= Issue command(s) to totalizer algorithm
= Issue command(s) to ramp/soak algorithm
= Select active set-point
= Cause output to track input 2 (only available

when input 2 is electrical and output is
current proportioning)

OUT ENAB

NO

YES

= Leave output at current value when

switching control mode to manual with
digital input

= Set output to value below when switching

control mode with digital input

OUT VAL

xx.x

x to xxx%
Limited by output mA high and low limits
above. Output generated when switching to
manual with digital input.

LOCKOUT

YES

NO

= Lockout front panel changes from auto to

manual control mode

= Allow front panel changes from auto to

manual control mode

See note above in 2.1.2.

ALLOWED

NO

YES

= Allows digital input to switch control mode

only on closed transition (auto to manual)

= Allows digital input to switch control mode

from manual to auto, or auto to manual

DI2 FUNC

RUN/STOP

RUN/HOLD

RUN/SKIP

= If DI closed: start profile at step 1

If DI open:

reset and stop on step 1

= If DI closed: continue from current step

If DI open:

stop and hold current step

= If DI closed: continue profile

If DI open:

skip current step, continue

67