Micromod MOD: Modcell 2050R Users Guide User Manual
Page 73

IB-23C650
SETUP
Table 3. Digital Input Setup Menu
Middle
Display
Bottom
Display
Entry Description
FUNCTION
NONE
AUTO/MAN
ALRM ACK
TOTALIZE
RAMPSOAK
SETP SEL
OUTP TRK
= Not used
= Switch control mode
= Global alarm acknowledge
= Issue command(s) to totalizer algorithm
= Issue command(s) to ramp/soak algorithm
= Select active set-point
= Cause output to track input 2 (only available
when input 2 is electrical and output is
current proportioning)
OUT ENAB
NO
YES
= Leave output at current value when
switching control mode to manual with
digital input
= Set output to value below when switching
control mode with digital input
OUT VAL
xx.x
x to xxx%
Limited by output mA high and low limits
above. Output generated when switching to
manual with digital input.
LOCKOUT
YES
NO
= Lockout front panel changes from auto to
manual control mode
= Allow front panel changes from auto to
manual control mode
See note above in 2.1.2.
ALLOWED
NO
YES
= Allows digital input to switch control mode
only on closed transition (auto to manual)
= Allows digital input to switch control mode
from manual to auto, or auto to manual
DI2 FUNC
RUN/STOP
RUN/HOLD
RUN/SKIP
= If DI closed: start profile at step 1
If DI open:
reset and stop on step 1
= If DI closed: continue from current step
If DI open:
stop and hold current step
= If DI closed: continue profile
If DI open:
skip current step, continue
67