Micromod MOD: Modcell 2050R Users Guide User Manual

Page 20

Advertising
background image

IB-23C650

INSTALLATION

Figure 3. Thermocouple Input Connections

GROUNDED

+

+

THERMOCOUPLE INPUT

Twisted or Shielded

Pair Thermocouple

Wire

Thermocouple

UNGROUNDED

Shield

Shield

Note

Note

Note:

Connect 100 ohm thermistor
supplied with instrument for
cold junction compensation.

Red

Wire

Thermocouple input specifications are:

Thermocouple: Automatic ranging and linearization

Type B*: 752 to 3002°F (400 to 1650°C)
*Performance accuracy is not guaranteed below 752°F.
Type E: –328 to 1832°F (–200 to 1000°C)
Type J: –328 to 2192°F (–200 to 1200°C)
Type K: –328 to 2498°F (–200 to 1370°C)
Type N: 32 to 2372°F (0 to 1300°C)
Type R & S: 32 to 3002°F (0 to 1650°C)
Type T: –328 to 752°F (–200 to 400°C)

Thermocouple resistance: 1000 ohms maximum

Sample Time: 0.25 seconds

Standards: Per NBS125 and IEC584

Resolution: 3 microvolts or one least significant digit

Accuracy:

Type J, K, E, T, N:

±2.7°F (1.5°C) of input

Type R, S, B: ±3.6°F (2.0°C) of input

Cold junction compensation: 100 ohm RTD

14

Advertising