Micromod MOD: Modcell 2050R Users Guide User Manual
Page 49

IB-23C650
SETUP
Table 1. Base Configuration
Middle
Display
Bottom
Display
Entry Description
CALIBRAT
Entry point for main board calibration. See
Calibration Data section for details on these
steps.
Caution: These are factory calibration values
and should be altered only on the advice of
authorized service personnel. Changing any or
all of the 4 calibration values will cause the
instrument to mark the main instrument
calibration valid.
•
•
•
•
•
•
•
•
•
CALIBRAT
Entry point for option board calibration. See
Calibration Data section for details on these
steps.
Note: Factory calibration values are shipped
with the option board and need to be entered
as part of installing a new board.
•
•
•
•
•
•
•
•
•
DATABASE
The
UP
key will be ignored unless the
configuration password is non-zero.
If
FACTORY1 DATABASE
is the prompt for
this step, a test data base will be loaded in
place of the default.
SURE?
YES
NO
This step is present only to guard against
accidentally defaulting the database. When the
database is defaulted, all configuration data is
written over with the factory default values.
The unit must then be reconfigured for the
desired control functions.
43