CALIBRATION DATA

Table 15. Main/Option Board Calibration (Base Configuration Menu)

Step

Step Description

Top

Display

17.3

Input 2 Ma. Resistance Ratio

UP

begins entry at most significant digit. Use

UP

or

DN

to set the digit, then

SCRL

to scroll to the

next digit. Repeat for all digits.

SCRL

advances to:

Step 17.3.1 if value was changed.
Step 17.4 otherwise.

INPUT 2

17.3.1

Are You Sure You Want to Change Input 2 Ma.
Res. Ratio?

UP

selects YES or

DN

selects NO.

SCRL

advances to:

Step 17.3 on NO. Step 17.4 on YES.

ARE YOU

17.4

Input 2 Circuit Compensation

UP

begins entry at most significant digit. Use

UP

or

DN

to set the digit, then

SCRL

to scroll to the

next digit. Repeat for all digits.

SCRL

advances to:

Step 17.4.1 if value was changed.
Step 17.5 otherwise.

INPUT 2

17.4.1

Are You Sure You Want to Change Process
Input Circuit Compensation?

UP

selects YES or

DN

selects NO.

SCRL

advances to:

Step 17.4 on NO. Step 17.5 on YES.

ARE YOU

17.5

Output 2 Current Ratio

UP

begins entry at most significant digit. Use

UP

or

DN

to set the digit, then

SCRL

to scroll to the

next digit. Repeat for all digits.

SCRL

advances to:

Step 17.5.1 if value was changed. Step 18 in
BASE CFG MENU otherwise.

OUTPUT 2

17.5.1

Are You Sure You Want to Change Output 2
Current Ratio?

UP

selects YES or

DN

selects NO.

SCRL

advances to:

Step 17.5 on NO. Step 18, Default Database
entry point, in BASE CFG MENU on YES.

ARE YOU