Micromod MOD: Modcell 2050R Users Guide User Manual
Page 171

IB-23C650
TUNING
Table 13. Autotune Procedure
Middle
Display
Bottom
Display
Entry Description
INCREASE
STEP SIZ
The ratio of process oscillation to hysteresis
value is too small for best results. Check tun-
ing constants. If desired, restart autotune with
a larger output step size or a smaller hysteresis
value. Hysteresis must be at least equal to,
and preferably greater than, process noise.
RESPONSE
LIMITED
The controller is using the high limit for
proportional band or reset. Check tuning
constants. The controller is using the newly
calculated constants. Because of process
characteristics, restart is not likely to improve
tuning constant calculations.
AUTOTUNE
FAILED
Autotune execution has been canceled, the
controller is in manual, and the output is at the
starting output value. A
PROCESS TOO
SLOW
, or a
DECREASE STEP SIZ
message
follows.
PROCESS
TOO SLOW
Autotune will not work on this process because
it is too slow.
DECREASE
STEP SIZ
The process has exceeded one of the
configured process trip-points. Restart
autotune with a smaller output step size or
expand the high and low trip-point of the
process variable.
165