Micromod MOD: Modcell 2050R Users Guide User Manual
Page 81

IB-23C650
SETUP
Table 4. Milliamp Output Setup Menu
Middle
Display
Bottom
Display
Entry Description
UP OUTPT
xx.x
–8.0 to 110.0. Limited by output high and low
limits above.
If heat/cool is used, output value (OV) can be
determined from heat output (HO) or cool
output (CO) and crossover value (CV):
OV (Heat) = CV + {[(100CV)xHO]/100}
OV (Cool) = CV [(CVxCO)/100]
VARIABLE
PROCESS
SETPOINT
INPUT 2
MANUAL
BUS_ONLY
NONE
= Retransmit the process variable on output 2
= Retransmit the active set-point variable on
output 2
= Retransmit input 2 on output 2
= Manually control output 2 from front panel
= Output 2 is controlled via the computer and
RS-485 Communications
= Fix second output at 0 mA.
PROC HI
or
SETPT HI
xxxx
–3000 to 30000.
Decimal placed per Inputs, Table 2.
Value of the retransmission variable, in
engineering units, which produces the 100%
current on output 2.
PROC LO
or
SETPT LO
xxxx
–3000 to 30000.
Decimal placed per Inputs, Table 2.
Value of the retransmission variable, in
engineering units, which produces the 0%
current on output 2.
MA. HIGH
xx.x
01.0 to 54.0 mA dc
The current produced by 100% output from the
control algorithm.
Example: 100% = 20 mA dc
MA. LOW
xx.x
0 to (mA high – 1) mA dc
The current produced by 0% output from the
control algorithm.
Example: 0% = 4 mA dc
75