IB-23C650

SETUP

Table 3. Digital Input Setup Menu

Middle

Display

Bottom

Display

Entry Description

ALLOWED

NO

YES

= Digital input transition selects any set-point

for which it is configured, except remote

= Digital input transition selects any set-point

for which it is configured

When both digital inputs are used for set-point
selection, this choice applies to both. They are
not independent.

ACTION

REVERSE

DIRECT

Causes a closed contact to be treated as an
open contact and vice versa

SEL LIST

LOC,LO2
LOC,LO3
LOC,LO4
LO2,LO3
LO2,LO4
LO3,LO4
LOC,REM
LO2,REM
LO3,REM
LO4,REM

L1,2,3,4
L1,2,3,R
L1,2,4,R
L1,3,4,R
L2,3,4,R

= When selecting with one digital input, for

digital input values 0 (Open), 1 (Closed)
(Remote options are only available if Input 2
is enabled)

= When selecting with two digital inputs, for

DI2/DI1 values of 00,01,10,11
Where R is remote set-point (remote options
are only available if Input 2 is enabled)