SETUP

Table 8. Set-Point Setup Menu

Middle

Display

Bottom

Display

Entry Description

MISSING

REM SETP

None.

UP SETPT

xxxx

–3000 to 30000, within local set-point limits

TRACKING

NO

YES

= Set-point tracking not activated
= Activate set-point tracking. Tracks process

input when controller in manual. No set-
point/process deviation when switching from
manual to auto.

Note: Local set-points 1-4 will not track if
configured to be ‘fixed’. Remote set-point
cannot track.