Micromod MOD: Modcell 2050R Users Guide User Manual

Page 79

Advertising
background image

IB-23C650

SETUP

Table 4. Milliamp Output Setup Menu

Middle

Display

Bottom

Display

Entry Description

**MENU**

None.

MA. HIGH

xx.x

01.0 to 54.0 mA dc
The current produced by 100% output from the
control algorithm.

(

i. e. ,100% = 20 mA dc)

MA. LOW

xx.x

0 to (mA high – 1) mA dc
The current produced by 0% output from the
control algorithm.

Example: 0% = 4 mA dc

HI LIMIT

xx.x

0.1 to 110.0% of heat output span
The maximum value for heat output.

HI LIMIT

xx.x

0.1 to 110.0% of cool output span
The maximum value for cool output.

HI LIMIT

xx.x

10.0 to 110.0% of mA output span
10.0 to 100% of relay output span
(limited to 50 mA maximum)

LO LIMIT

xx.x

–8% to (high limit – 1.0)% of mA output span
0% to (high limit – 1.0)% of relay output span
(limited to 0 mA minimum)

MANUAL

YES

NO

=Output HI and LO limits apply in manual or

output tracking.

= Output is not limited in manual or output

tracking.

OUTP SRC

LAST

FIXED

= Power up with the same output value as at

power down

= Power up with fixed value below

73

Advertising