Micromod MOD: Modcell 2050R Users Guide User Manual

Page 46

Advertising
background image

IB-23C650

SETUP

Table 1. Base Configuration

Step

Step Description

Top

Display

11

Totalizer Enable.

UP

selects YES or

DN

selects NO.

SCRL

advances to Step 12.

TOTALIZE

12

RS-485 Communications Enable.
(Requires Option Board)

UP

selects YES or

DN

selects NO.

SCRL

advances to Step 13.

RS-485

13

Tune Password.

UP

or

DN

sets tune password value (value must

be other than zero to lock configuration menus in
Step 19 ).

SCRL

advances to Step 14.

TUNE

14

Configure Password.

UP

or

DN

sets configure password value (value

must be other than zero to lock configuration
menus in Step 19 ).

SCRL

advances to:

Step 20 if you don’t have configuration access
with a non-zero password, or
Step 15 if you have config. access with a non-
zero password and a bad check sum was
found at most recent power up or check
summing is currently off, or
Step 16 otherwise.

CONFIG

15

Checksum the database.

UP

selects YES or

DN

selects NO.

SCRL

advances to:

Step 16 from NO, or
Step 15.1 from YES.

CHK SUM

15.1

Are You Sure You Want to Stop Check-
summing the Database?

UP

selects YES or

DN

selects NO.

SCRL

advances to Step 16.

ARE YOU