Micromod MOD: Modcell 2050R Users Guide User Manual
Page 43

IB-23C650
SETUP
Table 1. Base Configuration
Middle
Display
Bottom
Display
Entry Description
ACTION
DIRECT
REVERSE
=
relay output is open or mA output #2 is
MA.LOW at 0% displayed cool output and
relay is closed or mA output #2 is
MA.HIGH at 100% displayed cool output.
=
relay output is closed at 0% displayed cool
output and open at 100%, or mA output #2
is MA.HIGH at 0% and is MA.LOW at
100% displayed cool output.
CALIB
Valve position feedback (input 2) must be
calibrated prior to startup to use the controller
for position proportioning control.
The feedback signal always uses input 2
(option board required) and may be a slidewire
feedback, as shown in Figure 9, or other
electrical input.
OPEN POS
xxxxx
=
Valve Stem Position Feedback.
When this reaches a maximum value (i.e. stops
changing) the valve is fully open. Scrolling will
record this as the 100% open feedback value.
CLSD POS
xxxxx
=
Valve Stem Position Feedback.
When this reaches a minimum value (i.e. stops
changing) the valve is fully closed. Scrolling
will record this as the 0% open (100% closed)
feedback value.
CALIBRAT
> OPEN
37