SETUP

Table 3. Digital Input Setup Menu

Middle

Display

Bottom

Display

Entry Description

**MENU**

None.

INPUT 1

None.

FUNCTION

NONE

AUTO/MAN
ALRM ACK
TOTALIZE
RAMPSOAK
SETP SEL
OUTP TRK

= Not used
= Switch control mode
= Global alarm acknowledge
= Issue command(s) to totalizer algorithm
= Issue command(s) to ramp/soak algorithm
= Select active set-point
= Cause output to track input 2 (only available

when input 2 is electrical and output is
current proportioning)

OUT ENAB

NO

YES

= Leave output at current value when

switching control mode to manual with
digital input

= Set output to value below when switching

control mode to manual with digital input

OUT VAL

xx.x

x to xxx%
Limited by output mA high and low limits
above. Output generated when switching to
manual with digital input.

LOCKOUT

YES

NO

= Lockout front panel changes from auto to

manual control mode

= Allow front panel changes from auto to

manual control mode

Note: NO allows changes from front panel,
which may conflict with digital input state.
Digital input actions take place only at
‘transitions’ so that a subsequent front panel
override can take place if allowed.

61