8) description on terminal block, Sensor. must not be used unless o – Yokogawa IR200 User Manual

Page 23

Advertising
background image

3 - 10

IM 11G02M01-01E

(8) Description on terminal block

Terminal block 1

<TN1>

11

12

13

14

15

16

17

18

19

20

1

2

3

4

5

6

7

8

9

10

(M3.5 screw)

Unused

Unused

CH8 output
(AO)

CH7 output
(AO)

CH6 output
(AO)

CH1 output

(AO)

CH2 output

(AO

CH3 output

(AO)

CH4 output

(AO)

CH5 output

(AO)

Ϫ

ϩ

Ϫ

ϩ

Ϫ

ϩ

Ϫ

ϩ

Ϫ

ϩ

Ϫ

ϩ

Ϫ

ϩ

Ϫ

ϩ

Terminal block 1 <TN1>

Terminal block for analog output (non-isolated output)

Output

: 4 to 20 mA or 0 to 1 V DC

Between 1 – 2

: CH5 output

Between 3 – 4

: CH4 output

Between 5 – 6

: CH3 output

Between 7 – 8

: CH2 output

Between 9 – 10

: CH1 output

Between 11 to 14 : For internal connection. Must not be

wired. (Must not be used as junction
terminal.)

Between 15 – 16 : CH8 output

Between 17– 18

: CH7 output

Between 19– 20

: CH6 output

Terminal block 2 <TN2>

Between 1– 2

: For O

2

sensor input. (Input for our

Zirconia oxygen sensor or exernal
O

2

sensor. Must not be used unless

O

2

meter is added.)

Between 3 to12

: For internal connection. Must not be

wired. (Must not be used as junction
terminal.)

Between 13 – 14 : CH4 remote range changeover input

Between 15 – 16 : CH3 remote range changeover input

Between 17– 18

: CH2 remote range changeover input

Between 19– 20

: CH1 remote range changeover input

Note) High range is selected when

open. Low range is selected
when short-circuited. For
details of action, refer to “6.1
Changeover of range”.

Terminal block 2

<TN2>

11

12

13

14

15

16

17

18

19

20

1

2

3

4

5

6

7

8

9

10

(M3.5 screw)

Unused

CH4 remote range
changeover input
(DI)

CH3 remote range
changeover input
(DI)

CH2 remote range
changeover input
(DI)

CH1 remote range
changeover input
(DI)

Unused

Unused

Unused

Unused

O

2

sensor input

Ϫ

ϩ