Yokogawa IR200 User Manual

Page 26

Advertising
background image

3 - 13

IM 11G02M01-01E

Terminal block 5

<TN5>

11

12

13

14

15

16

17

18

19

20

1

2

3

4

5

6

7

8

9

10

(M3.5 screw)

Unused

Peak count alarm
output (DO)

CH4 alarm output
(DO)

CH3 alarm output

(DO)

CH2 alarm output

(DO)

CH1 alarm output

(DO)

Unused

Terminal block 5 <TN5>

1 and 11 – 14

: For internal connection. Must not

be wired. (Must not be used as
junction terminal.)

: CH3 alarm output. Conductive at 2–

3 and open at 3–

4 when set value is

exceeded. Open at 2– 3 and conduc-
tive at 3– 4 otherwise.

: CH2 alarm output. Conductive at 5–

6 and open at 6– 7 when set value is
exceeded. Open at 5– 6 and conduc-
tive at 6– 7 otherwise.

: CH1 alarm output. Conductive at 8–

9 and open at 9– 10 when set value
is exceeded. Open at 8– 9 and
conductive at 9– 10 otherwise.

: Peak count alarm contact output.

Conductive at 15 – 16 and open at
16 – 17 when preset peak count is
exceed. Otherwise, open at 15 – 16
and conductive at 16 – 17. For
setting and action, refer to instruc-
tion manual “6.6 Peak Alarm
Setting”.

: CH4 alarm output. Conductive at

18– 19 and open at 19– 20 when set
value is exceeded. Open at 18– 19
and conductive at 19– 20 otherwise.

Between 8– 9

and 9– 10

Between 15–16

and 16– 17

Between 18–19

and 19– 20

Between 5– 6

and 6– 7

Between 2– 3

and 3– 4