4 switch operating mode, Switch operating mode, Commissioning 4−43 – Festo Контроллер позиционирования CPX-CMAX User Manual

Page 121

Advertising
background image

4. Commissioning

4−43

Festo P.BE−CPX−CMA X−SYS−EN en 0908NH

4.6.4

Switch operating mode

When switching between record select and direct modes, Disable operation" is not
required. This can be used for optimising the control function.

[m]

SCON.OPEN = 1

[m]

SCON.OPEN = 0

Old operating mode

active

New operating mode

active

CCON.STOP = 0

[m]

[m]

[m]

[o]

[o]

Output data

Bytes 2 ... 8 = 0

New operating mode

setting

CCON.STOP = 1

CCON.OPM1 <> SCON.OPM1
OR
CCON.OPM2 <> SCON.OPM2

CCON.OPM1 = SCON.OPM1
AND
CCON.OPM2 = SCON.OPM2

If necessary: Enable drive again.

SCON.OPEN = 1

SCON.OPEN = 0

CCON
Bit B6 = CCON.OPM1
Bit B7 = CCON.OPM2

SCON
Bit B6 = SCON.OPM1
Bit B7 = SCON.OPM2

B7 B6 Operating mode

0

0

Record select

0

1

Direct mode

1

0

Commissioning

1

1

Parametrising

Wait for acknowledgment of switch.
During the switch, the status bytes
2 to 8 cannot be evaluated, since they cannot be definitely
allocated to one operating mode.

All bytes which depend on the operating mode are set to zero. This prevents old
setpoint data from affecting the CMAX, although this data might have a completely
different meaning in the new operating mode.

Assumption:
CCNON. ENABLE = 1
and CCON.STOP = 1

It is imperative that this action
be executed.

This action is a recommendation.
It does not have to be executed.

[m]

[o]