Festo Контроллер позиционирования CPX-CMAX User Manual

Page 135

Advertising
background image

5. Diagnostics and error handling

5−13

Festo P.BE−CPX−CMA X−SYS−EN en 0908NH

Malfunction group 2 ć Execution error

CPX error group 102 (CPX−MMI: [Record error] )

Continued

No.

Message

Cause/description

Error handling

Type

1)

27

Switching condition canĆ
not be reached during
movement

Switching position does
not lie between the start
position (last setpoint/
actual value at the time
of the switch) and the
new setpoint position or
both positions are the
same.

·

Check the switching
condition and correct,
if necessary. Check the
program sequence in
the PLC. After a stop or
an error, the previous
position must be apĆ
proached again.

Error
level: F1 (W)
Reset: R

The switching force is
not between the starting
force (last setpoint/
actual value at time of
switching) and the new
force setpoint.

28

Switching condition has
not been reached

Switching has not been
carried out yet MC was
reached before the
switching condition was
met.

·

Check the switching
condition. Parameterise
as warning, if
necessary.

Error
level: F1 (W)
Reset: R

1)

For the error level and reset type, see section 5.2.3.

Advertising