3. Electrical installation

3−14

Festo P.BE−CPX−CMA X−SYS−EN en 0908NH

3.4.2

Power supply concept, formation of power zones

The modular power supply concept of the CPX terminal allows
power zones to be formed.

Observe the following:

ć

The internal electronics of the VPWP and the digital posiĆ
tion measuring system and, if present, the sensor interĆ
face are supplied with power by the electronics/sensors
operating voltage supply (U

EL/SEN

).

The VPWP load supply and the VPWP outputs are supĆ
plied with power by the valve load supply (U

VAL

).

ć

The CMAX internally connects the contact rails 0 V

EL/SEN

to 0 V

VAL

of the CPX terminal.

ć

This means that the operating power supply for the
electronics/sensors (U

EL/SEN

) of the CPX terminal and

the CMAX load supply for the valves (U

VAL

) are no

longer electrically isolated.

ć

Complete electrical isolation (all poles) of the valve
supply of the VPWP is therefore

not possible, even in

conjunction with a CPX valve supply of type CPX−EV−V.

Note
Damage to components and operative malfunctions!

·

The CMAX must be supplied via the same potential
(common power supply unit) as the operating power
supply for the electronics/sensors (U

EL/SEN

) of the

CPX terminal (see also Fig. 3/3).

The CMAX always connects the 0 V supply for the elecĆ
tronics with the 0 V supply for the valves. This must be
observed when a CPX−GE−EV−V interlinking block is located
to the left of the CMAX because this can remove any intenĆ
tional electrical isolation.