5. Diagnostics and error handling

5−16

Festo P.BE−CPX−CMA X−SYS−EN en 0908NH

Malfunction group 3 ć Regulation error

CPX error group 103 (CPX−MMI: [Control error] )

Continued

No.

Message

Cause/description

Error handling

Type

1)

33

Target position outside
software or hardware
endpositions

Target position lies outĆ
side of the set software
end positions.

·

Check target position,
software end posiĆ
tions and project zero
point and correct.

Error
level: F1 (W)
Reset: R

Target position lies outĆ
side of the reachable
hardware end positions.

·

Check target position
and project zero point
and correct.

34

Set−point of tracking
mode outside limits

Target position lies outĆ
side of the set software
end positions.

·

Check setpoint posiĆ
tion, software end
positions and project
zero point and corĆ
rect.

Error
level: W (F1)
Reset: R

Setpoint position lies
outside of the reachable
hardware end positions.

·

Check setpoint posiĆ
tion and project zero
point and correct.

35

Pass the software end
position

2)

The drive was pushed
out of the valid range by
an external force.

·

If possible, prevent
external force.

Error
level: W (F1)
Reset: R

Controllers which are
not optimally set can
lead to considerable
overshooting.

·

Optimise the
controller, check
parameterisation,
carry out identificaĆ
tion again.

1)

For the error level and reset type, see section 5.2.3.

2)

The actual position exceeded a software end position during active position control.