5. Diagnostics and error handling

5−24

Festo P.BE−CPX−CMA X−SYS−EN en 0908NH

Malfunction group 6 ć Valve error

CPX error group 106 (CPX−MMI: [Error in valve] )

No.

Message

Cause/description

Error handling

Type

1)

60

Communication with valve
disturbed or valve not
available

Only the position measurĆ
ing system/sensor interĆ
face was found at
switch−on. The valve was
not detected.

·

Check the lines to the
valve.

·

Replace the valve.

Error level: F2
Reset: N

Communication between
CMAX and the valve was
interrupted.

·

Check the lines of the
axis string, valve and
sensor step−by−step and
exchange, if necessary.

61

Valve hardware is defecĆ
tive

The valve signals a hardĆ
ware error.

·

Replace the valve.

Error level: F2
Reset: N

Error while initialising the
valve.

·

Exchange the valve,
check the firmware
version of CMAX.

62

Overtemperature at valve

The valve signals overtemĆ
perature. (Ambient temĆ
perature too high).

·

Make sure there is
sufficient cooling.

Error level: F2
Reset: F

63

Valve jammed

The valve piston does not
move as expected.

·

Replace the valve.

·

Also check the air
quality (5 Ģ filter and
dry air).

Error level: F2
Reset: F

64

Valve load voltage outside
tolerance range (under−
voltage)

The valve signals a load
voltage which is too low.
Either the line between
CMAX and the valve is
defective or the valve is.

·

Check the cables on the
axis string.

·

Check the valve and exĆ
change, if necessary.

Error level: F2
Reset: F

1)

For the error level and reset type, see section 5.2.3.