1 defining the operating mode with ccon, Defining the operating mode with ccon – Festo Контроллер позиционирования CPX-CMAX User Manual

Page 95

Advertising
background image

4. Commissioning

4−17

Festo P.BE−CPX−CMA X−SYS−EN en 0908NH

4.5.1

Defining the operating mode with CCON

Operating mode

Description

Record select operating mode
ć Record select mode
(OPM1 = 0; OPM2 = 0)

The PLC selects a record from a record list stored in the CMAX.
A record contains all the parameters which are specified for a posiĆ
tioning job. The record number is transferred to the cyclical I/O data
as the setpoint or actual value.

Direct operating mode
ć Direct mode
(OPM1 = 1; OPM2 = 0)

The positioning job is transferred directly into the cyclical I/O data.
The most important setpoint values (position, speed, force) are
transferred here. Supplementary parameters (e.g. acceleration) are
defined via parameterisation.

Commissioning operating
mode
(OPM1 = 0; OPM2 = 1)

Commissioning functions (e.g. identification) can be executed and
parameters read or written. Positioning jobs are not possible.

Parametrising operating
mode
(OPM1 = 1; OPM2 = 1)

A parameter is transferred into the I/O data according to the FPC
protocol. Positioning jobs are not possible.

Tab. 4/2: Overview of CMAX operating modes

CCON

All the statuses which must be available in all operating
modes are controlled with control byte 1 (CCON).

Allocation of the control byte CCON (byte 1)

CCON

B7
OPM2

B6
OPM1

B5
LOCK

B4
ć

B3
RESET

B2
BRAKE

B1
STOP

B0
ENABLE

Operating mode
selection

Software
access
blocked

ć

Acknow−
ledge
malfuncĆ
tion

Release
brake

Stop

Enable
drive

SCON

Status byte 1 (SCON) signals the status of the CMAX in all
operating modes.

Allocation of the status byte SCON (byte 1)

SCON

B7
OPM2

B6
OPM1

B5
FCT_MMI

B4
24VL

B3
FAULT

B2
WARN

B1
OPEN

B0
ENABLED

Acknowledgement of
operating mode

Device
control
software

Load
voltage
applied

MalfuncĆ
tion

Warning

OperĆ
ation
enabled

Drive enĆ
abled