5. Diagnostics and error handling

5−11

Festo P.BE−CPX−CMA X−SYS−EN en 0908NH

Malfunction group 1 ć Execution error

CPX error group 101 (CPX−MMI: [Execution error] )

Continued

No.

Message

Cause/description

Error handling

Type

1)

16

Dynamic Identification
failed

Incorrect mass was
parameterised or transĆ
ferred to parameter 2.

2)

·

Check the mass and
data.

Error
level: F1
Reset: R

Too much mechanical
backlash in the system.

·

Check the system
structure.

Design not stable
enough.

·

Check the system
structure.

Used tubes are too long.

·

Place the valve closer
to the drive.

Compressed air is not
sufficiently stable.

·

Check the pressure
supply.

17

Identification not yet
executed

Static identification was
not executed at start of
record, during direct
mode or homing.

·

Static identification
executed

Error level: W
Reset: F

18

Clamping unit is still actiĆ
vated, operation enable
not possible

Operation enable
was granted
(CCON.STOP = 1),
although the clamping
unit was not yet reĆ
leased.

·

Cancel operation enĆ
able.

·

Release clamping unit.

Error level: W
Reset: F

19

Invalid change of
operating mode

Changing between reĆ
cord select and direct
modes during an active
positioning job
(SPOS.MC=0).

·

Switch only after
completed positionĆ
ing job
(SPOS.MC = 1)

Error
level: F1
Reset: R

Changing between reĆ
cord select and direct
modes and commissionĆ
ing or parametrising opĆ
erating mode while operĆ
ation enable is active
(CCON.STOP=1).

·

Only switch when
status is stopped".
Set CCON.STOP
= 0 and wait for
SCON.OPEN = 0 and
SPOS.MC = 1

1)

For the error level and reset type, see section 5.2.3.

2)

Parameter 2: Byte 4 ... 8 in commissioning operating mode.