5. Diagnostics and error handling

5−25

Festo P.BE−CPX−CMA X−SYS−EN en 0908NH

Malfunction group 6 ć Valve error

CPX error group 106 (CPX−MMI: [Error in Valve] )

Continued

No.

Message

Cause/description

Error handling

Type

1)

65

Valve operating voltage
outside tolerance range
(undervoltage)

The valve signals an
operating voltage which is
too low. Either the line beĆ
tween CMAX and the valve
is defective or the valve is.

·

Check the cables on the
axis string.

·

Check the valve and
exchange, if necessary.

Error level: F2
Reset: F

66

Overload at digital output
of valve

The valve signals an overĆ
load at the digital output.

·

Check the connections
and correct.

Error level: F2
Reset: F

67

Overload on 24V voltage
output of the valve

The valve signals an overĆ
load at the voltage output.

·

Check the circuitry and
correct.

Error level: F2
Reset: F

68

Warning: Overtemperature
at valve

The valve signals a high
operating temperature.
(Ambient temperature too
high).

·

Make sure there is
sufficient cooling.

Error level: W
Reset: F

1)

For the error level and reset type, see section 5.2.3.