I-1801 - tpdo2 communication parameter, I-1801/1, I-1801 – Lenze E84DGFCC User Manual

Page 104: I-1801/2, Communication manual 8400 motec canopen, Implemented canopen objects

Advertising
background image

Communication manual 8400 motec CANopen

Implemented CANopen objects

104

L

EDS84DMOTCAN EN 3.0 - 11/2011

I-1801 - TPDO2 communication parameter

Communication parameters for sending process data via TPDO2

For data telegram assignment and description of subindexes, see object

I-1800

.

How to change the identifier:

1. Deactivate identifier (set bit 31 to "1").
2. Change identifier.
3. Activate identifier (set bit 31 to "0").

Index:

I-1801

Name:

TPDO2 communication parameter

Subindex

Default setting

Setting range (min. value | unit | max. value)

Access

Data type

0: Highest subindex supported

5

- (read access only)

ro

U8

1: COB-ID used by TPDO

0x280 + node ID

0

4294967295 rw

U32

2: Transmission type

254

0

255 rw

U8

3: Inhibit time

0 ms

0

0.1 ms

65535 rw

U16

4: Reserved

-

- (reserved, read or write access results in error

message 0x06090011)

rw

U8

5: Event timer

0 ms

0

ms

65535 rw

U16

Subindex

Meaning

Code

0

The value 5 is permanently set.

• Max. 5 subindexesare supported.

-

1

TPDO2 identifier

• According to the "Predefined Connection Set", the

basic setting is: identifier = 0x280 + node ID

C00354/4

2

TPDO transmission type according to DS301 V4.02



Transmission type ( 52)

C00322/2

3

Minimum time between sending two identical TPDOs

(see DS301 V4.02).

-

5

Cycle time for PDO transmission with transmission type

"254".

C00356/2

C00369