Parameter | Name:

C00324 | CAN Tx inhibit time

Data type: UNSIGNED_16

Index: 24251

d

= 5EBB

h

Inhibit time for the transmission of the emergency telegram and the process data

Note:

If the "Asynchronous - manufacturer-specific/device profile-specific" transmission time is set, the transmission

cycle timer is reset to 0 if the transmission has been triggered in an event-controlled manner.

Example: Cycle time (

C00356/x

) = 500 ms, inhibit time = 100 ms, data change sporadically:

• In the case of a sporadical data change < 500 ms, due to the inhibit time set, transmission takes place as quickly

as possible every 100 ms (event-controlled transmission).

• In the case of a sporadical data change > 500 ms, due to the cycle time set, transmission takes place every 500 ms

(cyclic transmission).

• Mapping of the CANopen objects

I-1800/3

and

I-1801/3

(see DS301 V4.02).

Setting range

(min. value | unit | max. value)

0

ms

6500

Subcodes

Lenze setting

Info

C00324/1

0 ms

Inhibit time for emergency telegrams

C00324/2

0 ms

CAN1_OUT inhibit time

C00324/3

0 ms

CAN2_OUT inhibit time

;

Read access ; Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX ; COM … MOT

Parameter | Name:

C00345 | CAN error status

Data type: UNSIGNED_8

Index: 24230

d

= 5EA6

h

Display of the CAN error status
Selection list

(read only)

0 No Error
1 Warning ErrActive
2 Warning ErrPassive
3 Bus off
4 Reserved
5 Reserved

;

Read access … Write access … CINH … PLC-STOP ; No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT