Communication manual 8400 motec CANopen

Monitoring

Heartbeat protocol

70

L

EDS84DMOTCAN EN 3.0 - 11/2011

10.3.2

Parameter setting

Short overview of the parameters for the "Heartbeat" monitoring function:

Heartbeat producer time
Time interval for the transmission of the heartbeat telegram to the consumer(s).

 Parameterisable in

C00381

or via object

I-1017

. The parameterised time is rounded

down to an integer multiple of 5 ms.

 The heartbeat telegram is sent automatically as soon as a time > 0 ms is set.

Heartbeat consumer time
Monitoring time for the nodes (producers) to be monitored.

 Parameterisable in

C00386/1...n

or via object

I-1016

.

 The parameterised time is rounded down to an integer multiple of 5 ms and must have

a greater value than the heartbeat producer time of the node to be monitored.

 1 Heartbeat Producer can be monitored.
 The node address(es) of the nodes to be monitored is/are set in

C00385/1...n

or via

object

I-1016

, too.

Parameter

Info

Lenze setting

Assignment

Value Unit

Consumer

Producer

C00347/1...n

CAN status

of heartbeat producer 1

-

z

C00381

Heartbeat producer time

0 ms

z

C00385/1...n

CAN node address

of heartbeat producer 1

0

z

C00386/1...n

Heartbeat consumer time

for heartbeat producer 1

0 ms

z

C00592/5

Resp. to heartbeat event

No response

z