2 bus termination, Bus termination, Communication manual 8400 motec canopen – Lenze E84DGFCC User Manual

Page 25: 12 3 r s s r

Advertising
background image

EDS84DMOTCAN EN 3.0 - 11/2011

L

25

Communication manual 8400 motec CANopen

Installation

Electrical installation

A CAN network consisting of several segments contains repeaters (R) for connecting the

segments. The repeaters are provided with integrated bus terminations.



Consider the use of repeaters

( 28)

[5-3]

CAN network with repeaters

If no repeater is to be used at the end of the segment, the bus must be terminated by a bus

terminating resistor at the last node (S). The bus termination is supplied by the node itself.

5.2.2

Bus termination

The system bus (CANopen) must be terminated through a bus terminating resistor at the

first and last physical node (120 Ω).
In the case of the communication unit, the bus terminating resistor can only be installed

externally at the M12 connector. This has the advantage that the presence of the resistor

can be identified on the closed device.

E94YCPM012b

M

Z

Z

S

S

S

Z

Z

Z

Z

1

2

3

R

S

S

R

Note!

• The CANopen terminals (input and output) must be installed so that they are

closed. For this purpose either use a connecting cable, a closed terminating

resistor plug (M12 pins, 5-pole, A-coded), or a cap.

• The connecting cable and terminating resistor plug can be procured freely

from various cable manufacturers (e.g. Lapp or Turck).

• If you want to disconnect individual nodes, ensure that the bus terminations

at the cable ends remain active. Otherwise the bus may become instable.

• Observe that the bus terminator is no longer active when the terminating

resistor plug has been removed.

Advertising