Parameters for CANopen communication

76

L

EDS84DMOTCAN EN 3.0 - 11/2011

12.2

Parameters for CANopen communication

This chapter lists the CANopen parameters of the communication unit in numerically

ascending order.

C00322

C00323

Parameter | Name:

C00322 | Transmission mode CAN TxPDOs

Data type: UNSIGNED_8

Index: 24253

d

= 5EBD

h

TPDO transmission type according to DS301 V4.02

• The following transmission modes are supported:

–0: Synchronous and acyclic

–1 ... 240: Synchronous and cyclic

–252: Synchronous - only RTR

–253: Asynchronous - only RTR

–254: Asynchronous - manufacturer-specific

–255: Asynchronous - device profile-specific

• The basic setting for all PDOs is the "asychronous - manufacturer-specific" setting (254).

• Mapping of the CANopen objects

I-1800/2

and

I-1801/2

(see DS301 V4.02).

Setting range

(min. value | unit | max. value)

0

255

Subcodes

Lenze setting

Info

C00322/1

254

Transmission mode CAN1 OUT

C00322/2

254

Transmission mode CAN2 OUT

;

Read access ; Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX ; COM … MOT

Parameter | Name:

C00323 | Transmission mode CAN Rx PDOs

Data type: UNSIGNED_8

Index: 24252

d

= 5EBC

h

RPDO transmission type according to DS301 V4.02

• For the RPDO, it serves as monitoring setting in the case of sync-controlled PDOs.

• The following transmission modes are supported:

–0: Synchronous and acyclic

–1 ... 240: Synchronous and cyclic

–252: Synchronous - only RTR

–253: Asynchronous - only RTR

–254: Asynchronous - manufacturer-specific

–255: Asynchronous - device profile-specific

• The basic setting for all PDOs is the "asychronous - manufacturer-specific" setting (254).

• Mapping of the CANopen objects

I-1400/2

and

I-1401/2

(see DS301 V4.02).

Setting range

(min. value | unit | max. value)

0

255

Subcodes

Lenze setting

Info

C00323/1

254

Transmission mode CAN1 IN

C00323/2

254

Transmission mode CAN2 IN

;

Read access ; Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX ; COM … MOT