Communication manual 8400 motec canopen – Lenze E84DGFCC User Manual

Page 27

Advertising
background image

EDS84DMOTCAN EN 3.0 - 11/2011

L

27

Communication manual 8400 motec CANopen

Installation

Electrical installation

Segment cable length

2. Check that the segment cable length is not exceeded

The segment cable length is determined by the number of nodes and the cable

cross-section used. Without a repeater, the segment cable length corresponds to

the total cable length.

[5-2]

Segment cable length

3. Compare both values.

If the value determined from the

Segment cable length

[5-2]

table is smaller than

the required total cable length

Total cable length

[5-1]

, repeaters must be used.

Repeaters divide the total cable length into segments.

Selection example

Based on the given specifications, the following cable lengths/number of repeaters result

for a maximum of 63 nodes:

Maximum number of

nodes per segment

Cable cross-section

0.25 mm

2

0.5 mm

2

0.75 mm

2

1 mm

2

2

240 m

430 m

650 m

940 m

5

230 m

420 m

640 m

920 m

10

230 m

410 m

620 m

900 m

20

210 m

390 m

580 m

850 m

32

200 m

360 m

550 m

800 m

63

170 m

310 m

470 m

690 m

Given
• Cable cross-section:

0.5 mm

2

, according to

Specification of the bus cable

( 26)

• Number of nodes:

63

• Repeater:

Lenze repeater, type 2176 (cable reduction: 30 m)

Baud rate [kbps]

20

50

125

250

500

800

1000

Max. cable length [m]

4013

1575

600

275

113

38

13

Segment cable length [m]

270

270

270

270

113

38

13

Number of repeaters

15

6

2

1

-

-

-

Advertising