C00353 | can in/out cobid source, C00354 | cobid, C00355 | active cobid – Lenze E84DGFCC User Manual

Page 80: Y, define via code, C00353, That the identifiers of the pdos are to be, C00354/1, C00354/2, C00354/3, C00354/4

Advertising
background image

Communication manual 8400 motec CANopen

Parameter reference

Parameters for CANopen communication

80

L

EDS84DMOTCAN EN 3.0 - 11/2011

C00353

C00354

C00355

Parameter | Name:

C00353 | CAN IN/OUT COBID source

Data type: UNSIGNED_8

Index: 24222

d

= 5E9E

h

Identifier allocation procedure for the CANx_IN/OUT process data
Selection list

Info

0 COBID = C0350 + LenzeBaseID

COBID = device address + LenzeBaseID

1 COBID = C0350 + CANBaseID

COBID = device address + CANBaseID (

C00354/x

)

2 COBID = C0354/x

COBID = direct setting from

C00354/x

Subcodes

Lenze setting

Info

C00353/1

1

COBID source CAN1_IN/OUT

C00353/2

1

COBID source CAN2_IN/OUT

;

Read access ; Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX ; COM … MOT

Parameter | Name:

C00354 | COBID

Data type: UNSIGNED_32

Index: 24221

d

= 5E9D

h

Setting of the default COBID according to CANopen

• A change of the COBID will only become effective after a CAN reset node.



Identifiers of the process data objects ( 51)

Value is bit-coded:

Bit 0 COBID Bit0

... ...

Bit 10 COBID Bit10
Bit 11 Reserved

... ...

Bit 30 Reserved
Bit 31 PDO invalid

Subcodes

Lenze setting

Info

C00354/1

513 (0x00000201)

COBID CAN1_IN

C00354/2

385 (0x00000181)

COBID CAN1_OUT

C00354/3

769 (0x00000301)

COBID CAN2_IN

C00354/4

641 (0x00000281)

COBID CAN2_OUT

;

Read access ; Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX ; COM … MOT

Parameter | Name:

C00355 | Active COBID

Data type: UNSIGNED_16

Index: 24220

d

= 5E9C

h

Display of the COBID of the PDOs that is active in the CAN stack



Identifiers of the process data objects ( 51)

Display area

(min. value | unit | max. value)

0

2047

Subcodes

Info

C00355/1

Active COBID CAN1_IN

C00355/2

Active COBID CAN1_OUT

C00355/3

Active COBID CAN2_IN

C00355/4

Active COBID CAN2_OUT

;

Read access … Write access … CINH … PLC-STOP ; No transfer … PDO_MAP_RX … PDO_MAP_TX ; COM … MOT