EDS84DMOTCAN EN 3.0 - 11/2011

L

79

Communication manual 8400 motec CANopen

Parameter reference

Parameters for CANopen communication

C00350

C00351

C00352

Parameter | Name:

C00350 | CAN node address

Data type: UNSIGNED_8

Index: 24225

d

= 5EA1

h

Setting of the node address via parameters

• The node address can only be parameterised if the node address "0" is set via the DIP switches.

• A change of the node address will only become effective after a CAN reset node.



Setting the CAN node address ( 33)

Setting range

(min. value | unit | max. value)

Lenze setting

1

63 1

;

Read access ; Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX ; COM … MOT

Parameter | Name:

C00351 | CAN baud rate

Data type: UNSIGNED_8

Index: 24224

d

= 5EA0

h

Setting of the baud rate via parameters

• The baud rate can only be parameterised if the baud rate "0" is set via the DIP switches.

• A change of the baud rate will only become effective after a CAN reset node.



Setting the baud rate ( 32)

Selection list

(Lenze setting printed in bold)

0 500 kbps
1 250 kbps
2 125 kbps
3 50 kbps
4 1000 kbps
5 20 kbps

14 800 kbps

;

Read access ; Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX ; COM … MOT

Parameter | Name:

C00352 | CAN Slave/Master

Data type: UNSIGNED_8

Index: 24223

d

= 5E9F

h

The drive starts as CAN master after mains switching if the value "1" has been entered and saved here.
Selection list

(Lenze setting printed in bold)

0 Slave
1 Master

;

Read access ; Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX ; COM … MOT