Communication manual 8400 motec CANopen

Commissioning

Possible settings via DIP switch

32

L

EDS84DMOTCAN EN 3.0 - 11/2011

6.3

Possible settings via DIP switch

[6-1]

DIP switch

6.3.1

Setting the baud rate

The baud rate ...

 must be the same for all networked CANopen nodes;
 can be set via the DIP switches a ... c or via the »Engineer« (code

C00351

).



Settings in the Lenze »Engineer«

( 34)

The DIP switches serve to ...

Setting the baud rate

( 32)

(switches: a ... c)

Setting the CAN node address

( 33)

(switches: 1 ... 64)

Lenze setting: All switches OFF

Note!

• The DIP switches can only be accessed when the drive unit is detached from

the communication unit. Loosen the four fixing screws at the drive unit.

Observe the notes in the mounting instructions.

• Switch off the voltage supply of the controller and the external supply of the

communication unit before starting with the dismounting of the drive unit.

• The DIP switches are only read in when the device is switched on.

DIP switch position

Baud rate

c

b

a

ON

OFF

ON

20 kbps

OFF

ON

ON

50 kbps

OFF

ON

OFF

125 kbps

OFF

OFF

ON

250 kbps

OFF

OFF

OFF

500 kbps

ON

ON

OFF

800 kbps

ON

OFF

OFF

1000 kbps