Consider the use of repeaters, Communication manual 8400 motec canopen – Lenze E84DGFCC User Manual

Page 28

Advertising
background image

Communication manual 8400 motec CANopen

Installation

Electrical installation

28

L

EDS84DMOTCAN EN 3.0 - 11/2011

Consider the use of repeaters

Conclusion:

 A cable length of 450 m is not possible without installing a repeater.
 After 360 m (step 2), a repeater must be installed.

Result:

 The Lenze repeater, type 2176 (cable reduction: 30 m), is used
 Calculation of the max. cable length:

– First segment: 360 m
– Second segment: 360 m (according to the table

Segment cable length

[5-2]

( 27)

)

minus 30 m (cable reduction when a repeater is used)

 Max. possible cable length with one repeater: 690 m

– Now the required cable length is possible.

Note!

The use of an additional repeater is recommended as:
• Service interface

– Advantage: Trouble-free connecting during ongoing bus operation is

possible.

• Calibration interface

– Advantage: Calibration/programming units remain electrically isolated.

Given
• Baud rate:

125 kbps

• Cable cross-section:

0.5 mm

2

• Number of nodes:

28

• Cable length:

450 m

Steps

Cable length

See

1

Total cable length at 125 kbps:

600 m

Table

Total cable length

[5-1]

( 26)

2

Segment cable length for 28 nodes and a

cable cross-section of 0.5 mm

2

:

360 m

Table

Segment cable length

[5-2]

( 27)

3

Comparison: The value determined in

step 2 is smaller than the required cable

length of 450 m.

Advertising