EDS84DMOTCAN EN 3.0 - 11/2011

L

33

Communication manual 8400 motec CANopen

Commissioning

Possible settings via DIP switch

6.3.2

Setting the CAN node address

The node addresses must differ from each other in the case of several networked CANopen

nodes.
The node address can be set via DIP switches 1 ... 64 or via the »Engineer« with code

C00350

.

For the setting with

C00350

DIP switches 1 ... 64 must be set to OFF.

The labelling on the housing corresponds to the values of the individual DIP switches for

determining the node address.

The current address setting of the DIP switches is displayed in

C00349

.



DIP switch positions for setting the CAN node address

( 106)



Settings in the Lenze »Engineer«

( 34)

Note!

• The valid address range is 0 ... 63.
• If DIP switch 64 = ON (node address > 63), always node address 63 is used.

DIP switch

Node address

64

32

16

8

4

2

1

OFF

OFF

OFF

OFF

OFF

OFF

OFF

Value from

C00350

OFF

OFF

OFF

OFF

OFF

OFF

ON

1

OFF

...

...

...

...

...

...

...

OFF

ON

ON

ON

ON

ON

ON

63

ON

...

...

...

...

...

...

DIP switch

64

32

16

8

4

2

1

Switch position

OFF

OFF

ON

OFF

ON

ON

ON

Value

0

0

16

0

4

2

1

Node address

= Sum of the values = 16 + 4 + 2 + 1 = 23