Specification of the bus cable

We recommend the use of CAN cables in accordance with ISO 11898-2:

Observe the notes provided on the

Bus cable length

( 26)

!

5.2.4

Bus cable length

Total cable length

1. Check that the total cable length is not exceeded.

The total cable length is determined by the baud rate.

[5-1]

Total cable length

CAN cable in accordance with ISO 11898-2
Cable type

Paired with shielding

Impedance

120 Ω (95 ... 140 Ω)

Cable resistance/cross-section

Cable length ≤ 300 m

Cable length 301 ... 1000 m

70 mΩ/m / 0.25... 0.34 mm

2

(AWG22)

40 mΩ/m / 0.5 mm

2

(AWG20)

Signal propagation delay

5 ns/m

Note!

• It is absolutely necessary to comply with the permissible cable lengths.
• Please take into account the reduction of the total cable length due to the

signal delay of the repeater.



Consider the use of repeaters

( 28)

• Mixed operation refers to different nodes being connected to the same

network.

• If the total cable lengths of the nodes are different at the same baud rate, the

smaller value must be used to determine the maximum cable length.

Baud rate [kbps]

Max. bus length [m]

20

4013

50

1575

125

600

250

275

500

113

800

38

1000

13