I-1016 - consumer heartbeat time, I-1017 - producer heartbeat time, I-1017 – Lenze E84DGFCC User Manual

Page 95: The parameterised time is rounded, Object, I-1016, Communication manual 8400 motec canopen, Implemented canopen objects

Advertising
background image

EDS84DMOTCAN EN 3.0 - 11/2011

L

95

Communication manual 8400 motec CANopen

Implemented CANopen objects

I-1016 - Consumer heartbeat time

Monitoring time for the nodes to be monitored via heartbeat.



Heartbeat protocol

( 69)

The parameterised time is rounded down to an integer multiple of 5 ms and must have a

greater value than the heartbeat producer time of the node to be monitored.

[13-4] Data telegram assignment

I-1017 - Producer heartbeat time

Time interval for the transmission of the heartbeat telegram to the consumer(s).



Heartbeat protocol

( 69)

 The parameterised time is rounded down to an integer multiple of 5 ms.
 The heartbeat telegram is sent automatically as soon as a time > 0 ms is set. In this case

the monitoring function "Node Guarding" is deactivated.

 This object relates to code

C00381

.

Index:

I-1016

Name:

Consumer heartbeat time

Subindex

Default setting

Setting range (min. value | unit | max. value)

Access

Data type

0: Highest subindex supported

1

- (read access only)

ro

U16

1 ... n: Consumer heartbeat time

0

0

65535 rw

U16

Subindex

Meaning

Lenze code

0

Number of nodes to be monitored

1 ... n

Node ID and heartbeat time of the node to be monitored Node ID:

C00385/x

Heartbeat time:

C00386/x

8th byte

7th byte

6th byte

5th byte

Data 4

Data 3

Data 2

Data 1

Bit 31 ... bit 24

Bit 23 ... bit 16

Bit 15 ... bit 0

0

Reserved

Node ID

Heartbeat time

in [ms]

Index:

I-1017

Name:

Producer heartbeat time

Subindex

Default setting

Setting range (min. value | unit | max. value)

Access

Data type

0: Producer heartbeat time

0

0

ms

65535 rw

U16

Advertising