EDS84DMOTCAN EN 3.0 - 11/2011

L

43

Communication manual 8400 motec CANopen

Data transfer

Communication phases/network management

7.2.3

Parameterising the Inverter Drives 8400 motec as CAN master

If the initialisation of the system bus and the associated status change from "Pre-

operational" to "Operational" is not effected by a higher-level host, the Inverter Drive 8400

motec can instead be defined to be a "quasi" master to execute this task.
The controller is configured as CAN master in

C00352

.

 Being the CAN master, the controller sets all nodes connected to the bus (broadcast

telegram) to the "Operational" communication status with the "Start remote node"

NMT telegram. Only in this communication status data can be exchanged via process

data objects.

 A delay time can be set in

C00356/1

, which must expire after mains switching before

the controller transmits the "Start remote node" NMT telegram.

Tip!
Master functionality is only required during the initialisation phase of the drive

system.

Parameter

Info

Lenze setting

Value Unit

C00352

CAN slave/master

Slave

C00356/1

CAN delay boot-up - Operational

3000 ms

Note!

The changes of the master/slave operation in

C00352

will not be activated until

• another mains switching of the controller
or
• the "Reset node" or "Reset communication" NMT telegram has been

transmitted to the controller.

The "CAN reset node" device command (C00002/26) is provided as an alternative

to the "Reset node" NMT telegram for the reinitialisation of the CAN-specific

device parameters.