Specification of the bus cable

17

L

EDS84DPBUS EN 2.0 - 09/2010

4.2

Specification of the bus cable

Please follow the specifications of the PROFIBUS user organisation (PNO) for bus cables:

Bus cable length
The bus cable length depends on the baud rate used:

Tip!
For high baud rates we recommend to consider the application of optical fibres.
Advantages of optical fibres:
• External electromagnetic interferences on the transmission path remain

ineffective.

• Bus lengths of several kilometres are also possible with higher baud rates.

The bus length is ...
– independent of the baud rate;
– dependent on the optical fibre used.

Area

Values

Cable resistance

135 ... 165 Ω/km, (f = 3 ... 20 MHz)

Capacitance per unit length

30 nF/km

Loop resistance

< 110 Ω/km

Core diameter

> 0.64 mm

Core cross-section

> 0.34 mm

2

Cores

Double twisted, insulated and shielded

Baud rate

Length

9.6 ... 93.75 kbps

1200 m

187.5 kbps

1000 m

500 kbps

400 m

1500 kbps

200 m

3000 ... 12000 kBit/s

100 m

Note!

The baud rate depending of the data volume, cycle time and number of stations

should only be selected as high as required for the application.