Monitorings

Permanent interruption of PROFIBUS communication

10

Monitorings

10.1

Permanent interruption of PROFIBUS communication

If the PROFIBUS communication is interrupted permanently, e.g. by cable breakage or

failure of the PROFIBUS master, no process data is transmitted to the slave being in the

"DATA_EXCHANGE" status.
After the watchdog monitoring time determined by the PROFIBUS master has expired, the

response parameterised in

C13880

is executed in the controller.

The process data are treated according to the setting in

C13885

. (The data last sent by the

master may be used or set to zero.)

Preconditions for a controller (slave) response

A monitoring time of 1 ... 65534 ms for the "Data_Exchange" status (

C13881

) is set.

A value of "65535 ms" (Lenze setting) deactivates the monitoring.

For the slave, a response is set in

C13880

(Lenze setting: "No response").

The slave is in the "Data_Exchange" status.

In the master, the watchdog monitoring time must be configured correctly.

If one of these preconditions is not met, the response to the absence of cyclic process data

telegrams from the master is not executed.



Settings and displays in the »Engineer«