Communication manual 8400 protec PROFIBUS
Parameter data transfer
DP-V1 parameter data channel (PROFIdrive profile)
59
L
EDS84DPBUS EN 2.0 - 09/2010
Parameter response after faultless read request
Parameter response after read error
Byte 1
Byte 2
Byte 3
Byte 4
Request reference
Response identification
Axis
Number of indices
0xXX
0x01
0x00
0x01
(mirrored)
Parameter read
(mirrored)
Byte 5
Byte 6
Format
Number of values
0x03
0x01
Integer16
1 value
Byte 7
Byte 8
Value
High byte
Low byte
0x00
0x2B
Value read = 0x 00 2B = 43 x 1 (internal factor) = 43 [°C]
Byte 1
Byte 2
Byte 3
Byte 4
Request reference
Response identification
Axis
Number of indices
0xXX
0x81
0x00
0x01
(mirrored)
Parameter not read
(mirrored)
Byte 5
Byte 6
Format
Number of values
0x44
0x01
Fault
Error code without additional
information
Byte 7
Byte 8
Error code
High byte
Low byte
For meaning see chapter "