Safety communication timeout [0x01bc6610]

Safety parameter timeout [0x01bc6611]

Safety Init error [0x01bc6612]

Profibus watchdog: Monitoring time expired [0x01bc8130]

Profibus: "Data_Exchange" status exited [0x01bc8131]

Response (Lenze setting printed in bold)

Setting: not possible

…

None … System fault … Fault … Trouble … Quick stop by trouble : Warning locked … Warning … Information

Cause

Remedy

This is an error message which occurs during each safe

parameter download.

Acknowledge error.

Response (Lenze setting printed in bold)

Setting: not possible

…

None … System fault … Fault … Trouble … Quick stop by trouble : Warning locked … Warning … Information

Cause

Remedy

Safety option SO20/SO30 does not respond to a

PROFISafe parameterisation telegram (PRM data) within

a set time interval (200 ms).

Activate safety option SO20/SO30.

Response (Lenze setting printed in bold)

Setting: not possible

…

None … System fault … Fault … Trouble … Quick stop by trouble : Warning locked … Warning … Information

Cause

Remedy

• Communication with safety option SO20/SO30 could

not initialised properly.

• The master did define a safety application but a

connection to the safety option has not been

detected internally.

Activate safety option SO20/SO30.

Response (Lenze setting printed in bold)

Setting:

C13880/1

(; adjustable response)

:

None … System fault ; Fault … Trouble ; Quick stop by trouble ; Warning locked … Warning ; Information

Cause

Remedy

Permanent interruption of communication to the

PROFIBUS master.

• See also chapter "

Permanent interruption of

PROFIBUS communication

"

( 64)

.

Check cables and terminals.

Response (Lenze setting printed in bold)

Setting:

C13880/1

(; adjustable response)

:

None … System fault ; Fault … Trouble ; Quick stop by trouble ; Warning locked … Warning ; Information

Cause

Remedy

Data exchange via PROFIBUS has been stopped.

• See also chapter "

Permanent interruption of

PROFIBUS communication

"

( 64)

.

Check cables and terminals.

The slave must receive new parameterisation and

configuration files from the master for again being able

to exchange data.