Communication manual 8400 protec PROFIBUS
Diagnostics
Advanced diagnostic message
73
L
EDS84DPBUS EN 2.0 - 09/2010
11.4.1
Example 1: Error in parameter data "Incorrect PROFIsafe target address"
This error was caused while the communication of the PROFIBUS master was established
because the projected PROFIsafe target address in the PROFIBUS master does not
correspond to the set address anymore.
11.4.2
Example: Error in standard device "Short circuit (OC1)"
Byte
Value (hex)
Meaning
1
x Standard data (PRM_Fault)
...
6
7
0A Block length of the extended diagnostics = 10 bytes
8
81 Status message
9
00 Slot 0
10
01 Status coming
11
40 PROFIsafe error "0x0040" (64)
• GSG: "F address differ to F_Dest_Add"
12
00
13
00 No other error message
...
...
16
00
Byte
Value
[hex]
Description
1
x Standard data (PRM_Fault)
...
6
7
0A Block length of the extended diagnostics = 10 bytes
8
81 Status message
9
00 Slot 0
10
01 Status coming
11
00
12
00
13
0B Error message 0x11C4000B ("Short circuit (OC1)")
• Error type: "Warning locked"
• Subject area: 0x11C4 (current)
• Error ID: 0x000B
Thus, the error number "0x11C4000B" means: An overcurrent has been detected in
the "current" subject area causing a "Warning locked" error response which must be
unlocked after the error has been removed.
14
00
15
C4
16
11