Diagnostics

Advanced diagnostic message

73

L

EDS84DPBUS EN 2.0 - 09/2010

11.4.1

Example 1: Error in parameter data "Incorrect PROFIsafe target address"

This error was caused while the communication of the PROFIBUS master was established

because the projected PROFIsafe target address in the PROFIBUS master does not

correspond to the set address anymore.

11.4.2

Example: Error in standard device "Short circuit (OC1)"

Byte

Value (hex)

Meaning

1

x Standard data (PRM_Fault)

...

6
7

0A Block length of the extended diagnostics = 10 bytes

8

81 Status message

9

00 Slot 0

10

01 Status coming

11

40 PROFIsafe error "0x0040" (64)

• GSG: "F address differ to F_Dest_Add"

12

00

13

00 No other error message

...

...

16

00

Byte

Value

[hex]

Description

1

x Standard data (PRM_Fault)

...

6
7

0A Block length of the extended diagnostics = 10 bytes

8

81 Status message

9

00 Slot 0

10

01 Status coming

11

00

12

00

13

0B Error message 0x11C4000B ("Short circuit (OC1)")

• Error type: "Warning locked"

• Subject area: 0x11C4 (current)

• Error ID: 0x000B

Thus, the error number "0x11C4000B" means: An overcurrent has been detected in

the "current" subject area causing a "Warning locked" error response which must be

unlocked after the error has been removed.

14

00

15

C4

16

11